Description, device design, dimension drawing
2.4 Status displays and signaling
SITOP PSU100S
12 Operating Instructions, 02.2013, C98130-A7589-A1-3-7629
2.4 Status displays and signaling
6EP1322-2BA00, 6EP1323-2BA00, 6EP1332-2BA20
6EP1333-2BA20, 6EP1334-2BA20, 6EP1336-2BA10
Status display LED green for 24 V O.K. or 12 V O.K.
Signaling contact Relay contact (NO contact, contact rating 30 V AC / 0.5 A, 60 V DC / 0.3 A, 30 V DC / 1 A)
for 24 V O.K. or 12 V O.K.
(3%$H[DPSOH
(3%$(3%$
(3%$(3%$
(3%$
Figure 2-5 Status displays and signaling
Signaling 6EP1322-2BA00
6EP1323-2BA00
6EP1332-2BA20
6EP1333-2BA20
6EP1334-2BA20
6EP1336-2BA10
LED ⑤ lights up green
Signaling contact ③,
contacts 13-14 closed
Normal operation,
Output voltage
>10 V ±0.5 V
Normal operation,
Output voltage
>20 V ±0.5 V
Normal operation,
Output voltage
>20 V ±0.5 V
LED ⑤ dark
Signaling contact
③,
contacts 13-14 open
(inactive position)
Overload operation or power
supply voltage missing
Overload operation or power
supply voltage missing
Overload / hiccup operation,
power supply missing or the
device has tripped due to
overtemperature (reset
possible with power OFF for
approx. 30 min)