Technical data
6.1 Input
SITOP PSU100S
40 Operating Instructions, 02.2013, C98130-A7589-A1-3-7629
6EP1332-2BA20 6EP1333-2BA20 6EP1334-2BA20 6EP1336-2BA10
Protection in the line
feeder cable (IEC 898)
required: Circuit
breaker, C
characteristic, 3 A
required: Circuit
breaker, C
characteristic, 6 A
required: Circuit
breaker, C
characteristic, 10 A
required: Circuit
breaker, C
characteristic, 10 A
or
Circuit breaker
3RV2411-1JA10
(120 V) or 3RV2411-
1FA10 (230 V)
Overvoltage strength - - - 2.3 × Ue rated, 1.3 ms
6EP1322-2BA00 6EP1323-2BA00
Input 1-phase, AC
Rated voltage Ue rated 120 / 230 V
Voltage range 85-132 / 170-264 V
automatic range switchover Yes
Connect/shutdown threshold,
typical
82 V / 66 V 66 V / 63 V
Power failure buffering at
Ia rated, min
20 ms 20 ms
Power-failure buffering at 93 / 187 V
Rated line frequency 50/60 Hz
Line frequency range 47...63 Hz
Input current / at rated value of
input voltage 120 V
1.73 A 3.24 A
Input current / at rated value of
input voltage 230 V
0.99 A 1.41 A
Switch-on current limitation
(+25 °C), max.
45 A 60 A
I²t, at 120 V AC, max. 0.3 A
2
s 1.6 A
2
s
I²t, at 230 V AC, max. 1.0 A
2
s 5.6 A
2s
Integrated input fuse Fuse T 3,15 A Fuse T 6 A
Protection in the line feeder
cable (IEC 898)
required: Circuit breaker, C
characteristic, 3 A
required: Circuit breaker, C
characteristic, 6 A