Installation
5.1 Line-side connection
SITOP PSU300S
32 Manual, 12.2016, C98130-A7587-A1-7-7629
Required line-side protection
6EP1433-2BA20 3-pole coupled miniature circuit breaker (IEC 898) characteristic C, 3 - 16 A
or
3RV2011-1DA10 circuit breaker, thermal overload release setting: 3 A
or
3RV2711-1DD10 circuit breaker (branch circuit protection according to UL 489)
6EP1434-2BA20 3-pole coupled miniature circuit breaker (IEC 898) characteristic C, 3 - 16 A
or
3RV2011-1DA10 circuit-breaker, setting of the thermal overcurrent release: 3 A
or
3RV2711-1DD10 circuit-breaker (branch circuit protection according to UL 489)
6EP1436-2BA10 3-pole coupled miniature circuit breaker (IEC 898) characteristic C, 6 - 16 A
or
3RV2011-1DA10 circuit-breaker, setting of the thermal overcurrent release: 3 A
or
3RV2711-1DD10 circuit-breaker (branch circuit protection according to UL 489)
6EP1437-2BA20 3-pole coupled miniature circuit breaker (IEC 898) characteristic C, 10 - 16 A
or
3RV2011-1DA10 circuit-breaker, setting of the thermal overcurrent release: 3 A
or
3RV2711-1DD10 circuit-breaker (branch circuit protection according to UL 489)
The protective conductor of the line supply must be connected at the PE terminal.
Other country-specific regulations may have to be observed when installing the device.