EasyManua.ls Logo

Siemens SITOP PSU300S - Protection and Monitoring; Mean Time Between Failures (MTBF)

Siemens SITOP PSU300S
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
6.5 Protection and monitoring
SITOP PSU300S
Manual, 12.2016, C98130-A7587-A1-7-7629
43
6.5
Protection and monitoring
6EP1433-2BA20
(24 V/5 A)
6EP1434-2BA20
(24 V/10 A)
6EP1436-2BA10
(24 V/20 A)
6EP1437-2BA20
(24 V/40 A)
Output overvoltage
protection
in the case of an internal fault U
out
< 35 V
Current limitation, typ.
6.6 A
13 A
25.5 A
50 A
Property of the out-
put/short-circuit proof
Yes
Short-circuit protection
Constant current characteristic
Electronic trip, automatic restart
Continuous short-
circuit current /
rms value / maximum
8 A 16 A 7 A 14 A
Continuous short-
circuit current / rms
value / typical
Remark
6.6 A
Overload capability
150 % I
out rated
up to
5 s/min
13 A
Overload capability
150 % I
out rated
up to
5 s/min
-
Overload capability
150 % I
out rated
up to
5 s/min
-
Overload capability
150 % I
out rated
up to
5 s/min
6.6
MTBF
6EP1433-2BA20
(24 V/5 A)
6EP1434-2BA20
(24 V/10 A)
6EP1436-2BA10
(24 V/20 A)
6EP1437-2BA20
(24 V/40 A)
Mean Time Between
Failures
SN29500:
> 500000 h (typ.
1500000 h) at 40 °C,
rated load, 24 hour
operation
SN29500:
> 500000 h (typ.
1450000 h) at 40 °C,
rated load, 24 hour
operation
SN29500:
> 800000 h at 40 °C,
rated load, 24 hour
operation
SN29500:
> 500000 h (typ.
700000 h) at 40 °C,
rated load, 24 hour
operation

Related product manuals