© Siemens AG Österreich, AT-1210 Vienna, Austria. All rights reserved. 8 von 8 SITOP UPS 500S
A5E51289135, 12.2021 SITOP UPS 501S
Vorschriften / Standards:
ATEX
6EP1933-2EC51-8AA0:
II 3G Ex ec nC IIC T4 Gc
WARNING: SEPARATE EXPANSION MODULE IN NON-HAZARDOUS AREAS ONLY!
Harzardous Areas: An enclosure / cabinet rated min. IP54 must be provided in the final installation.
The enclosure / cabinet must be in accordance with the requirement of EN 60079-0:2009 and/or EN60079-7:2010
DIP switches shall not be used in operation or while a hazardous area may be present
Only locking USB-cable type (Partno: Y-Con IP20LOCK-104 cable assy Distributor: Yamaichi) shall be used
WARNUNG
ANSCHLÜSSE NUR IN NICHT-EXPLOSIVER UMGEBUNG TRENNEN!
SCHALTERBETÄTIGUNG NUR IN NICHT-EXPLOSIVER UMGEBUNG DURCHFÜHREN!
Der Signalstecker darf in Ex Bereichen nur mit zusätzlichen Befestigungen verwendet werden um der EN 60079-7 zu genügen.
WARNING
SEPARATE TERMINALS IN NON-HAZARDOUS AREAL ONLY!
ACTUATE SWITCHES IN NON-HAZARDOUS AREAS ONLY!
The signal plug must not be used without additional fixings in explosive atmospheres to fulfill the requirements according EN 60079-7.
6EP1935-5PG01-8AA0:
II 3G Ex ec IIC T4 Gc
WARNING: SEPARATE EXPANSION MODULE IN NON-HAZARDOUS AREAS ONLY!
Harzardous Areas: An enclosure / cabinet rated min. IP54 must be provided in the final installation.
The enclosure / cabinet must be in accordance with the requirement of EN 60079-0:2009 and/or EN60079-7:2010
WARNUNG
ANSCHLÜSSE NUR IN NICHT-EXPLOSIVER UMGEBUNG TRENNEN!
WARNING
SEPARATE TERMINALS IN NON-HAZARDOUS AREAL ONLY!
© Siemens AG Österreich, AT-1210 Vienna, Austria. All rights reserved.
Liefermöglichkeiten und technische Änderungen vorbehalten
Availability and technical specifications subject to change without prior notice