Fig. 6: Measures against moisture penetration
Caution:
Do not hold SITRANS LVL200E on the tuning fork. P articularly with
ange or tube versions, the tuning fork can be damaged just by the
weight of the instrument. Transport coated instruments very carefully
and avoid touching the tuning fork.
Remove the packaging or the protective cover just before installation.
The process tting must be sealed if there is gauge or low pressure in
the vessel. Before use, check if the seal material is resistant against
the measured product and the process temperature.
The max. permissible pressure is specied in chapter "Technical data"
or on the type label of the sensor.
The vibrating level switch is a measuring instrument and must be
treated accordingly. Bending the vibrating element will destroy the
instrument.
Warning:
The housing must not be used to screw the instrument in! Applying
tightening force can damage internal parts of the housing.
Use the hexagon above the thread for screwing in.
Transport
Pressure/Vacuum
Handling
SITRANS LVL200E - CONTACTLESS ELECTRONIC SWITCH 13
4 Mounting
33839-EN-100908