8 8PQ9800-7AA76
Conexión a
Connection on
Puntos de
conexión
Connection
points
Tamaño de unión
atornillada
Size of screwed
joints
Máx. sección de conductor o terminal de cable
admisible* (DIN 46235) [mm
2
]
Max. permissible cable cross-section or cable
lug* (DIN 46235) [mm
2
]
Par de apriete
[Nm]
Tightening torque
[Nm]
Compartimento 250A
Compartment 250A
1
M10
120
40
Compartimento >250A 630A
Compartment >250A 630A
1
M12
240
70
Barra PE vertical en el
compartimento de conexión de
cables
Vertical PE bar in cable connection
compartment
M12
240
70
Barra N(PEN) vertical en el
compartimento de conexión de
cables
Vertical N(PEN) bar in cable
connection compartment
M12
240
70
* La conexión de cables se realiza en salidas con forma 1, 2b y 4a sin medición de la corriente directamente en el aparellaje..
* With outgoing feeders with form 1, 2b, 4a, the cable connection is directly established at the switching device without current measurement.
Tornillo de cabeza hexagonal DIN EN ISO 4014 M10 oder M12-8,8
Hexagonal bolt DIN EN ISO 4014 M10 or M12-8.8
Arandela Belleville DIN 6796-10/12-FSt
Strain washer DIN 6796-10/12-FSt
Arandela ISO 7089-10/12
Washer ISO 7089-10/12
Tuerca hexagonal ISO 4032-M10/M12-8
Hexagonal nut ISO 4032-M10/M12-8
Fuelle (fijar con bridas para cables)
Rubber bellow (to be fixed with cable tie)

Other manuals for Siemens Sivacon S8

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Sivacon S8 and is the answer not in the manual?

Siemens Sivacon S8 Specifications

General IconGeneral
BrandSiemens
ModelSivacon S8
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals