The following events (telegrams) are used:
Report on current status (for COV repetition)
Rising slope (start of short or long pulse)
Repeat, long pulse active
Short double-click completed
Start short/long double-click
Start long double-click (two clicks with one long pulse at start)
Long double-click completed
Dual click (both buttons pressed simultaneously)
Normally, preparameterized buttons are used that are customized for the blinds/lighting
applications to be used.
If individual parameterization is required, the function provides great flexibility to
implement any operating philosophy.
The following parameters are available:
1 or 2 (simple/dual button)
Pulse length 0.1...25.5 s (increment 0.1 s)
Repeat length 0.1...25.5 s (increment 0.1 s)
Double-click length 0.1...25.5 s (increment 0.1 s)
Stop Long Enable Sends Tg 6 at the end of a long
Falling slope for long pulse
Disabled
Stop Long Double
Sends Tg 11 at the end of a long
Falling slope for long double-click (Tg
Disabled
Repeat Enable Repeats Tg 5 with interval of tr
Sends no Tg 5 Enabled
ShortDoubleClick
Enable
Sends Tg7, Tg8, Tg9, if short or
long/short double-click is identified
(second rising slope before
Sends no Tg 7, Tg 8, Tg 9.
Also no status transition to first pulse.
Disabled
LongDoubleClick
Enable
Sends Tg 10, if long double-click
identified (second rising slope after
Sends no Tg 10 and no Tg 11.
Also no status transition to Long
Disabled
DualClick Enable Sends Tg12, Tg13, if both buttons
Sends no Tg 12, Tg 13. Also no status
Disabled