5.4  Maintained contact, bistable 
(BO Bistable NO / NC)  
 
 
On/off switching of devices and loads. 
Interruption of the power supply or the bus communications: the last state of the relays 
is maintained (bistable relays). In addition, the module supports setting of a backup 
state as well as a time delay before this backup state becomes effective. 
–  Light control 
–  Control of subsystems with uninterruptible operation 
 
•  The function is supported by module type TXM1.6RL only 
•  The function requires one I/O point 
•  The module has N/O contacts only 
•  The relay contacts are especially adapted for light applications 
 
Process value 
 
I/O status LED  
 
 
Relay contact 
 
The signal operation can be selected: Relay (Default), Relay_NA (NA = normally active). 
 
In case of bus failure (Masterdown), where the DC 24 V module supply is intact, the 
following backup states can be parameterized: 
–  No  (Same effect as Value Off) 
–  Value  (On / Off) 
–  Keep  Same value as before the fault (= default) 
–  Delay before the backup state becomes effective: 
(0...6553s, default 120s, steps of 0.1s).  
 
Parameterizing can be made during operation. 
 
A powerfail DC 24 V always induces a bus failure - see above. 
 
In case of powerfail AC 24 V (Powerdown AC 24 V), the following backup states can 
be parameterized: 
–  No  (Same effect as Value Off) 
–  Value  (On / Off) 
–  Keep  Same value as before the fault (= default) 
 
Parameterizing can be made during operation. 
 
This function is available with relay type TXM1.6RL only.  
It supports changing to backup values even when the module supply is lost, not only in 
case of lost communications. 
•  For this purpose, the AC 24 voltage on the bus is monitored. This monitoring is fast 
enough to make the relays take their backup positions before the DC 24 V supply 
breaks down. 
•  As the relays are bistable, they stay in the backup position even without DC 24 V 
supply.