EasyManua.ls Logo

Siemens VGD20.253U - Page 2

Siemens VGD20.253U
14 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TechnicalInstructions VGDSeriesDoubleValves
DocumentNumberCC1N7631us
November08,2017
Page2 SiemensAGBuildingTechnologiesDivision
Features
AllModels
ULlisted,FMapproved,CSAcertified,IRIapprovable,ISO9001and14000certifie d.
CE,Australianapprovedversionsavailable
¼“inchNPTpressuretapsontheinletandoutletandbetweenmainvalves(seeTable2
fordetails)
Stainlesssteelmeshinletfilterprotectsthevalveseat(s)aswell
asdownstream
components
Dualstemguidesensureprecisediscalignmentandtightshutoff
ValvesinconnectionwithSKPxx.xxxUactuatorsopenslowlyandcloserapidly
VGD20.xxxUmodels
CompactVGD20.xxxUdoublevalvebodiesconsistof2safetyshutoffvalvesinseries.
Thefirst(inlet)valvehasaflatvalvediscapplicableforsafetyshutofffunctiononly.
Thesecond(outlet)valvehasacontouredvalvediscforusewithpressureregulating
actuators(SKP2x.xxxU,SKP5x.xxxU,SKP7x.xxxU)
A
1inchNPTventconnectionbetweenthevalves
EachVGD20.xxxUdoublevalverequires2threadedmountingflanges(AGFxx.xxU).Each
flangeincludesthenecessaryinstallationhardware(bolts, nutsandOring).Eachmounting
flangehasa¼inchNPT pressuretap.Theflangescanbepremountedontothepipe,and
thenboltedontotheVGD20.xxxUgasvalvebody.Thisfeatureeliminatestheuseofpipe
unionsandpermitsthegasvalveassemblyto beeasilyremovedfromagastrain
Connectingpatternofthe1...2inchAGFxx.xxUflangesareidentical.Thisspacepermits
anyAGFxx.xxUflangetobemountedtoanyVGD20.xxxUvalvebody
NOTE:
VGD20.xxxUvalvesandAGFxx.xxUflangesmustbeorderedasseparateitems(see
Tables2and3).
VGD40.xxxUmodels
CompactVGD40.xxxUdoublevalvebodiesconsistof2safetyshutoffvalvesinseries
Eachindividualsafety shutoffvalvehasdoubleseatstoachievehighflow
Patentedseatconstructionwithindividualclosingspring foreachseattoassurereliable
shutoffandhighcloseoffpressurerating
Fullportventlineconnectionplatesareavailable
NOTE:
VGD40.xxxUvalvesandAGA40.xxxxUventconnectionplatesmustbeorderedas
separateitems(seeTables2and3).