TechnicalInstructions VGDSeriesDoubleValves
DocumentNumberCC1N7631us
November08,2017
Page2 SiemensAGBuildingTechnologiesDivision
Features
AllModels
ULlisted,FMapproved,CSAcertified,IRIapprovable,ISO9001and14000certifie d.
CE,Australianapprovedversionsavailable
¼“‐inchNPTpressuretapsontheinletandoutletandbetweenmainvalves(seeTable2
fordetails)
Stainlesssteelmeshinletfilterprotectsthevalveseat(s)aswell
asdownstream
components
Dualstemguidesensureprecisediscalignmentandtightshut‐off
ValvesinconnectionwithSKPxx.xxxUactuatorsopenslowlyandcloserapidly
VGD20.xxxUmodels
CompactVGD20.xxxUdouble‐valvebodiesconsistof2safetyshut‐offvalvesinseries.
Thefirst(inlet)valvehasaflatvalvediscapplicableforsafetyshut‐offfunctiononly.
Thesecond(outlet)valvehasacontouredvalvediscforusewithpressureregulating
actuators(SKP2x.xxxU,SKP5x.xxxU,SKP7x.xxxU)
A
1‐inchNPTventconnectionbetweenthevalves
EachVGD20.xxxUdouble‐valverequires2threadedmountingflanges(AGFxx.xxU).Each
flangeincludesthenecessaryinstallationhardware(bolts, nutsandO‐ring).Eachmounting
flangehasa¼‐inchNPT pressuretap.Theflangescanbepre‐mountedontothepipe,and
thenboltedontotheVGD20.xxxUgasvalvebody.Thisfeatureeliminatestheuseofpipe
unionsandpermitsthegasvalveassemblyto beeasilyremovedfromagastrain
Connectingpatternofthe1...2inchAGFxx.xxUflangesareidentical.Thisspacepermits
anyAGFxx.xxUflangetobemountedtoanyVGD20.xxxUvalvebody
NOTE:
VGD20.xxxUvalvesandAGFxx.xxUflangesmustbeorderedasseparateitems(see
Tables2and3).
VGD40.xxxUmodels
CompactVGD40.xxxUdouble‐valvebodiesconsistof2safetyshut‐offvalvesinseries
Eachindividualsafety shut‐offvalvehasdoubleseatstoachievehighflow
Patentedseatconstructionwithindividualclosingspring foreachseattoassurereliable
shut‐offandhighclose‐offpressurerating
Fullportventlineconnectionplatesareavailable
NOTE:
VGD40.xxxUvalvesandAGA40.xxxxUventconnectionplatesmustbeorderedas
separateitems(seeTables2and3).