TechnicalInstructions VGDSeriesDoubleValves
DocumentNumberCC1N7631us
November08,2017
Page6 SiemensAGBuildingTechnologiesDivision
Specifications
Approvals
Agencyapprovals/standards UL/429,FM/7400,
CSA/ANSIZ21.21/CSA6.5C/I
IRIapprovable
AgencymarksapplyonlyforVGDxx.xxxUseries
gasvalvebodiesassembledwithSKPxx.xxxU
actuators.
Operating
environment
Maximumoperatingpressure SeeTable2
Maximumbackpressure(differential) VGD20.xxxU:2psi(150mbar)
VGD40.xxxU:4psi(300mbar)
Close‐offpressure SeeTable2
Permissiblegastemperature 14°Fto140°F(‐10°Cto60°C)
Permissibleoperatingtemperature 14°Fto140°F(‐10
°Cto60°C)
Use
SiemensgasvalvesareinaccordancewithUL429.
Thevalveisusedas:
‐ Safetyshutoffvalve(inconnectionwithSKP15.xxxU)
‐ Controlvalvewithsafetyshutofffunction(inconnectionwithSKP25.xxxU,SKP5x.xxxUor
SKP7x.xxxU)
Perm.mounting
position
7631z01us/0815
Operatingpressure
SeeTypesummary
Typesofgases
Suitablenaturalgases,propane,butaneandair
FormoreinformationseeUse.
Strainer
Built‐in,meshsize0.9mm