Page EN-6 XCT-8 Sanitary Transducer– INSTRUCTION MANUAL 7ML19985HX62
English
Interconnection
Cable Extension
Applies to the MiniRanger Plus and SITRANS LU/AiRanger series of transceivers.
Connect the supplied cable to a junction box and use RG–62 A/U coaxial cable from there
to the transceiver. This setup is effective for combined runs up to 365 m (1200 ft).
Twisted Pair Extension
Applies to the MultiRanger 100/200 transceiver. Extend the cable using 18 AWG shielded /
twisted pair.
Notes:
Installation shall only be performed by qualified personnel and in accordance
with local governing regulations.
Do not route cable openly. Run cable separately in a grounded metal conduit
to protect it from ambient electrical noise.
Use the supplied shielded, 3-wire cable to connect the transducer to the
Siemens Milltronics transceiver. Supplied cable lengths are 1 m (3 ft).
Seal all thread connections to prevent the ingress of moisture.
Do not run cable near high voltage or current runs, contacts, or SCR control
drives.
The terminal blocks on the transceiver are described in the transceiver
manual.
Siemens
Milltronics
transceiver
junction box
white
black
junction box
drain / shield