VH / VK Electrical connection
Technical changes reserved - 25 -
3.1 Plug connector EN 175301-803-A
IMPORTANT
To guarantee the type of protection IP 65 according to EN 60529, the connect-
ing cable has to have a sheathing diameter of between 4.5 and 10 mm.
Furthermore, ensure that all gaskets
, and at the plug connector are in-
serted correctly.
Loosen the central screw M3x35 and disconnect the cable socket from the plug
connector ( Fig. 1).
Remove the central screw from the cable socket .
Open the core of the cable socket with a screwdriver or similar tool ( Fig. 2).
Loosen the screwed cable gland M16x1.5 ( Fig. 3).
Fig. 1
Fig. 2
Fig. 3
Insert the connection cable through the screwed cable gland , the pressure ring and
the rubber insert into the cable socket ( Fig. 4).
Connect the wires as shown in the connection diagram below ( p. 26, Fig. 7)
Press the core into the cable socket until it locks into place.
Put the central screw in the cable socket and tighten the screwed cable gland ( Fig. 5).
Put the cable socket on the connector and tighten the central screw ( Fig. 6).
Fig. 4
Fig. 5
Fig. 6