VH / VK Technical Data
Technical changes reserved - 31 -
Type
VKS
VK3
Process variables
Nominal pressure
PN 10
Medium
(non-freezing)
0…20 °C (PN 10 / PVC pipe
section)
0…60 °C (PN 2,5 / PVC pipe
section)
-25…100 °C
Ambient
(do not store <4 °C)
0…60 °C (PVC pipe section)
-25…70 °C (VK3)
Max. permanent temperature
load of the cable
-/-
Max. 70 °C
Max. 100 °C (optional)
Electrical characteristics
Electrical connection
Plug connector
DIN EN 175301-803-A
incl. cable socket
Plug connector
DIN EN 175301-803-A
incl. cable socket with 2 LEDs
(optional)
*1
Sensor plug M12x1 (4-pin) (op-
tional)
1.5 m PVC sheathed cable
Wire cross-section
-/-
0.75 mm
2
Switching current
Max. 1 A
Switching voltage
Max. 230 VAC, 48 VDC
Rating
Max. 26 VA, 20 W
Degree of protection
(EN 60529)
IP 65
Protection class
(EN 60730-1)
Class II
*1 Switching voltages 24 V...230 V AC/DC ±20 %.
Type
VHS…X
VH3…X
Process variables
Nominal pressure
PN 25
Medium
(non-freezing)
-25…100 °C
Ambient
(do not store <4 °C)
-25…70 °C
Max. permanent temperature
load of the cable
Max. 70 °C