23

The fifth red LED is on steady:
Too High discharge pressure,
higher than 33 bar (460 PSI)
For the first 2 times, machine will
automatic reset when pressure
drop down. and the machine will
stop when high temperature occurs
the third time, ice machine will stop,
Reset mode:
Open the front panel, And press
MODE button that can go to start up
cycle.
Both the third yellow LED and forth
red LED are blinking fast:
Ice thickness sensor fault
When machine start, if PC board
detect the ice thickness ON,
machine will stop.
Reset mode:
Open the front panel, And press
MODE button that can go to start up
cycle.
Both the fourth red LED and second
green LED are blinking fast:
5 times too long Freeze Cycle
time
Reset mode:
Open the front panel, And press
MODE button thant can go to start
up cycle.