SIME FORMAT WALL HUNG BOILERS
MODEL 34i AND MODEL 34e
REF: INSTALLATION INSTRUCTIONS 19/02/04
2
GENERAL DATA
– Heating Data
Heat Output Input
(Adjustable) (Adjustable)
Format 34i
11.2 – 34KW 45 – 145MJ/hr
Format 34e
11.2 – 34KW 45 – 145MJ/hr
– General Specifications
FORMAT 34i – 34e
Main burner injectors
No off 15
Dia for Natural gas mm 1.45
Dia for LPG mm 0.85
Water Capacity
l(gal) 4.7 (1.00)
Burner pressure Natural gas
Maximum kPa 0.71kPa
Minimum kPa 0.09kPa
Burner pressure LPG (Propane)
Maximum kPa 2.41 kPa
Minimum kPa 0.50 kPa
Static head
Maximum bar (psi) 3.0 (43.5)
Minimum bar (psi) 0.5 (7.3)
Weight
Empty kg (lb) 40 (88)
Total (full) kg (lb) 44.7 (98)
Electrical supply
230V – 50Hz, Fused at 3A
Internal fuse
Line: F 1.6A
Maximum power consumption
Watt 160
Maximum gas consumpt. (Natural gas)
m³/h 3.68
Maximum gas consumpt. (Propane)
kg/h 2.74 – 2.70
Max. working temperature
°C (F) 95 (203)
Integral exp. Vessel capacity
L (gal) 8 (1.76)
TABLE 4
Gas Supply Min. Pressure Max. Pressure
Natural Gas 0.09kPa 0.71kPa
Propane Gas 0.50kPa 2.41kPa
Nominal Gas Consumption 145 mj/h