55
are not correct (make sure the
cables are placed on terminals 6
and 7 of the boiler terminal board).
The circulation pump is blocked,
unblock it.
Boiler operates only at nominal pres-
sure and does not reduce pressure.
Check whether there is voltage at
both ends of coil.
The coil has a break in the winding;
replace.
The rectifier card that supplies the
coil is interrupted; replace.
There is no differential on setting of
the two contacts of the regulating
thermostat; replace.
Check calibration of reduced pres-
sure adjusting screw (4 fig. 11) of
coil assembly.
The boiler gets dirty easily causing
scaling of cast iron exchanger and
cutting off of smoke stat.
Check that the flame of the main
burner is well regulated and that
gas consumption is proportional to
boiler output.
Poor ventilation of premises where
boiler is installed.
Flue with insufficient draught or not
meeting requirements.
The boiler works at too low tempe-
ratures. Adjust the boiler thermo-
stat to higher temperatures.
Thermostat switches boiler back
on with too high temperature dif-
ference.
Replace regulating thermostat
since it is out of calibration.

Other manuals for Sime RMG 70 Mk.II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sime RMG 70 Mk.II and is the answer not in the manual?

Sime RMG 70 Mk.II Specifications

General IconGeneral
BrandSime
ModelRMG 70 Mk.II
CategoryBoiler
LanguageEnglish

Related product manuals