EasyManua.ls Logo

Sime RX 26 BF - Outlet Terminal Positioning

Sime RX 26 BF
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.9 POSITIONING OF OUTLET
TERMINALS
The outlet terminals for forced draught
systems may be located on the outer
walls of the building.
Table 2 shows approximate, non-binding
minimum distances to be met for a buil-
ding of the type shown in fig. 6.
41
IT
ES
PT
GB
max 0,5 m
max 0,5 m
C12
B52
C52
B52
C32
C42
C82
B22
min. 700
Fig. 5
LIST OF ACCESSORIES THAT ALLOW THE
CONFIGURATIONS INDICATED ARE SUPPLIED
ON REQUEST:
Separate flue kit code 8089905
90° elbow MF code 8077410 (6 pz.)
90° insulated elbow MF code 8077408
90° elbow MF with take-off points
code 8077407
Extension L. 1000 code 8077309 (6 pz.)
Insulated e
xtension L. 1000 code 8077306
Extension L. 500 code 8077308 (6 pz.)
Outlet terminal code 8089501
Int.-est. ring kit code 8091500
Inlet terminal code 8089500
45° elbow MF code 8077411 (6 pz.)
Condensation outlet L. 135 code 8092800
Doubler fitting code 8091400
Tile with articulated joint code 8091300
Roof outlet terminal L. 1390 code 8091201
Tee condensation outlet code 8093300
WARNING:
- The outlet and intake ducts of type C52 cannot
be located on opposite walls.
- Types B22-B52 refer to the outlets of one
discharge duct only because suction is from
the environment.
TABLE 2
Siting of terminal Appliances from 7 to 35 kW
(distances in mm)
A - below openable window 600
B - below ventilation opening 600
C - below eaves 300
D - below balcony (1) 300
E - from adjacent window 400
F - from adjacent ventilation opening 600
G - from horizontal or vertical soil or drain pipes (2) 300
H - from corner of building 300
I - from recess in building 300
L - from ground level or other treadable surface 2500
M - between two terminals set vertically 1500
N - between two terminals set horizontally 1000
O - from a surface facing without
openings or terminals 2000
P - as above but with openings and terminals 3000
1)
Terminals below a practicable balcony must be located in such a way that the total path of the smoke from its outlet point from the terminal to its outlet
point from the external perimeter of the balcony, including the height of possible railings, is not less than 2000 mm.(?)
2) When siting terminals, where materials that may be subject to the action of the combustion products are present in the vicinity, e.g., eaves, gutters and
downspouts painted or made of plastic material, projecting timberwork, etc., distances of not less than 1500 mm must be adopted, unless adequate shiel-
ding is provided to guard these materials.
Fig. 6

Related product manuals