1/2 Doc. version 1.0
Indoor Isolated Callpoint
Installation
The Indoor Isolated Callpoint is an addressable indoor manual callpoint.
The callpoint signals the condition of a switch contact that is operated by
pressing on a deformable element. After activation the deformable element
is not destroyed and the callpoint can be reset.
The unit features a short-circuit isolator and meets the requirements of
EN54 Pt. 11 and EN54 Pt. 17.
Details of the Status LED and activation are on Page 2.
Item Order Number
MCP - Isolator Indoor 4099-5210
Resettable element (pack of 1) 515.001.127
Back box 515.001.021
1 Connect an 801AP MX Service Tool or an 850EMT into the
programming port, noting the orientation. Now program the unit with
the ID defined in the site configuration.
2 Implement the mounting method, for example:
Use the dedicated back box (order number above). Fix this to the
wall as a surface mount.
Use a standard back box with fixing holes at 60.3 spacing, such as a
standard UK single gang back box (BS4662). The box must be at
least 25 mm deep. This will probably be let into the wall as a flush
mounting option.
3 Route the loop wiring through the back box.
4 Connect the loop wiring to the push-fit connector as shown.
5 Remove the callpoint sliding front plate and deformable element
assembly. This is described in “To replace the deformable element”
below.
6 Connect the push-fit connector
7 Fix the callpoint to the back box using screws through the now-exposed
fixing holes.
8 Re-fit the front plate assembly. Slide it into position then push upwards
until it clicks into place.
Status LED
Press here to
activate
Loop -
Programming
Port
Push-fit
Connector
Loop +
Loop +
Loop -