PROCEDURE
To silence the Sonalert, place the NORMAL/SI-
LENCE switch in the SILENCE position.
When the power is restored, the green NORMAL
POWER lamp illuminates, amber TROUBLE lamp
out, Sonalert sounds (“ring-back”).
To silence the Sonalert, place the NORMAL/SI-
LENCE switch in’ the NORMAL position.
ZONE TROUBLE
(Example: An open occurs in an alarm initiating
circuit.)
Amber ZONE lamp illuminated, amber TROU-
BLE lamp illuminated, Sonalert sounding.
PROCEDURE:
To silence the Sonalert, place the NORMAL/SI-
LENCE switch in the SILENCE position.
When the alarm circuit “trouble” condition is re-
paired, the amber ZONE lamp goes out, amber
TROUBLE lamp out,
Sonalert sounds (“ring-
back”).
To silence the Sonalert, place the NORMAL/SI-
LENCE switch in the NORMAL position.
COMMON SYSTEM TROUBLE
(Example: An open occurs in a supervised pan-
el.)
Amber TROUBLE lamp illuminated, Sonalert
sounding.
PROCEDURE:
To silence the Sonalert, place the NORMAL/SI-
LENCE switch in the SILENCE position.
When the
“trouble” is repaired, the amber
TROUBLE lamp goes out and the Sonalert sounds
(“ring-back”).
To silence the Sonalert, place the NORMAL/SI-
LENCE switch in the NORMAL position.