9
7. e pump has been pre-lubricated with heavy oil
prior to shipment. Prime the system by using the
hand pump (Option 010 or 015) to transfer fuel
from the main tank to the Day Tank. If the Day
Tank is not equipped with a hand pump, remove
the tank inlet priming tee plug and ll the entire
inlet line with fuel. Replace the tee plug. Ener-
gize the Day Tank pump/motor by placing the
Day Tank mode selector switch in the automatic
position. Ensure that fuel is exiting the pump by
watching the clear pump outlet tubing. If not,
repeat this procedure and prime the pump also at
the pump priming tee. Make sure all unused Day
Tank holes are plugged, all pipe connections are
secure and no leaks are present. e Day Tank is
now ready for unattended automatic operation.
If the Day Tank has been stored for extended
periods of time pre-lube the pump with oil at the
pump priming tee.