IDNet Device Types (continued)
IDNet Error Messages
MCOI TrueAlarm ionization/CO sensor (standard base)
MCOIS TrueAlarm ionization/CO sensor (sounder base)
MCOH TrueAlarm heat/CO sensor (standard base)
MCOHS TrueAlarm heat/CO sensor (sounder base)
MCOPH TrueAlarm photo/heat/CO sensor (standard base)
MCOPHS TrueAlarm photo/heat/CO sensor (sounder base)
ANAMON 4-20ma Analog Monitor ZAM
STANDARD BASE Standard TrueAlarm base (no head inserted)
SOUNDER BASE TrueAlarm sounder base (no head inserted)
RELAY BASE TrueAlarm relay base (no head inserted)
ISOLATOR BASE TrueAlarm isolator base (no head inserted
CO BASE TrueAlarm CO sensor base (no head inserted)
CO SOUNDER
BASE
TrueAlarm CO sensor base with sounder (no head inserted)
UNKNOWN
DEVICE
Unrecognized device type
Type Description
INVALID ADDRESS A device was found at one of the following
addresses: 0, 251-255. The IDNet channel only
supports addresses 1-250.
DUPLICATE ADDRESS More than one device was found set to the same
address.
OUT OF RANGE A TrueAlarm sensor was found to have an analog
value that is out of range. This is most likely a dirty
sensor heat. Replace or clean the head.
HEAD MISSING A sensor head is not installed in a TrueAlarm base.
UNKNOWN DEVICE The TSIT has encountered a device that it is unable
to recognize. This occurs for several reasons:
More than one device is set to the same
address (run a duplicate address test).
Bad device.
A newer device type was found that is not
supported by the version of your TSIT
software.