A: Under the condition of T1≥T +1℃(2°F),compressor will be running
B:Under the condition of T1≤T +1℃(2°F),the unit will be switched off,compressor will be
off too
C:Under the condition of T1≤T +1℃(2°F),the compressor and internal motor system
will be switching back to the original setting
Note: When compressor is off, cooling operation light is splashing(0.5second per time)When the
compressor is running, the operation light will be turned on
10.5.1.3 During the cooling mode, the upper fan system can be set into auto,high,medium,low and
auto fan mode
High
Medium
Low
internal ambient temperature℃(°F)
set point temperature 2(3) 4(6)
10.5.1.4 Cooling mode,lower fan system is working together with compressor
10.5.2 Dehumidification mode( DH display)
10.5.2.1Upper fan system is operated in low fan. Lower fan is working together with the
compressor
10.5.2.2 Dehumidification mode.
A. Indoor temperature≤0℃,compressor will be off
B.0℃<indoor temperature≤20℃,compressor will be on for 15 min and stop for 3 min
C.indoor temperature>20℃compressor will be on for 30 min and stop for 3 min
We only can check the indoor temperature after such operation finishes after every week,
Note: When compressor is stop, the dehumidification indication light is on.
10.5.3Heating mode
10.5.3.1Heating mode: set point temperature range is 15~25℃(60~80°F),starting temperature
is 20℃(68°F)
10.5.3.2 Heating mode, compressor working condition
A. Under the condition of T3-T1≥+1℃(2°F)compressor will be turned on