DC Inverter Duct Type Air Conditioner  Installation and Operation Manual
21
(continued)
Fig.18 Quiet function setting
Note:
1. During quiet function, fan speed is un-adjustable.
2. When turning on auto  quiet  function, the unit  will enter  quiet running state according to temperature 
difference  between  room  temperature  and  setting  temperature.  In  this  case,  fan  speed  is  adjustable.  If 
temperature difference  between room temperature and  setting temperature  ≥ 4°C,  fan will keep its  current 
speed; if 2°C≤temperature difference ≤3°C; fan speed will be reduced by one grade ,but if it is at minimum 
grade, it is un-adjustable.; if temperature difference ≤1°C, fan speed will be at minimum grade
3. In auto quiet mode, fan speed can not be raised but reduced. If high fan speed is manually adjusted, auto 
quiet mode will quit.
4. There is not auto quiet function in fan or dry mode. Quiet off is default after power failure and then power 
recovery.
5. If quite function is set, turbo function will be canceled.
4.14 Field Functions
Under off-state of the unit, press Function and Timer buttons continuously for 5s to go to the debugging 
menu. Press Mode button to adjust the setting items and ▲ or ▼ button to set the actual value. 
4.14.1 Ambient Temperature Sensor Setting
In eld setting mode, press Mode button to adjust the temperature displayed location displaying 00, and 
press ▲ or ▼ button to adjust setting state at timer displayed location. There are 3 types for selection:
 ●  Indoor ambient temperature is that at return air inlet (01 is displayed at timer displayed location)
 ●  Indoor ambient temperature is that at the place of screen (02 is displayed at timer displayed location)
 ●  Return air inlet temperature sensor shall be selected for cooling, dry and fan modes and wired controller 
temperature sensor (03 is displayed at timer displayed location) shall be selected for heating and auto modes. 
4.14.2 Three Grades of Speed for Indoor Fan
In field setting mode, press Mode button to adjust the temperature displayed location displaying 01 and 
press ▲ or ▼ button to adjust setting state at timer displayed location. There are 2 types for selection:
 ●  3 low grades (LCD displays 01)
 ●  3 high grades (LCD displays 02)
Three low grades indicate high, medium and low grades and 3 high grades indicate super-high, high and