42
Installation and Maintenance
Service Manual
(1) Capacitor charge fault (Fault with outdoor unit) (AP1 below refers to the outdoor control panel)
Main Check Points:
●Use AC voltmeter to check if the voltage between terminal L and N on the wiring board is within 210VAC~240VAC.
●Is the reactor (L) correctly connected? Is the connection loose or fallen? Is the reactor (L) damaged?
Fault diagnosis process:
Outdoot Unit
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Turn on the unit 
and wait 1 minute
Use DC voltmeter 
to measure the 
voltage on the two 
ends of electrolytic 
capacitor 
Voltage higher than 200V?
Fault with the voltage 
testing circuit on 
control panel AP1
Replace the control 
panel AP1
Measure the AC voltage between 
terminal 
L and N on wiring board 
XT(power supply)
Voltage within 
210VAC~250VAC?
Shut down the power
and repair the power
supply to restore the
range
210VAC~250VAC
power on and
restart the unit
If the fault is 
eliminated?
Shut down the power and wait 20 mi
nutes;  
or use DC voltmeter to measure the voltage 
on the two ends of capacitor , until the 
 voltage  is lower than 20V
Check the 
connection of reactor 
(L in the Electrical 
Wiring Diagram)
If the wiring of 
reactor L
 is normal?
Connect the reactor 
Laccording to Elec-
trical Wiring Diagr-
am correctly
 
Re-energize and
turn on the unit
If the fault is 
eliminated?
End
Replace the control 
panel AP1