- 23 - 
6.2.  Outdoor Unit Errors 
Current errors of the outdoor unit are displayed in the last position of the main menu of the 
SCMI-01.4 module. The  first  line  contains the title  Error  and  the  second line  contains  four 
two-digit hexadecimal error codes (or the sum of these codes, if multiple errors occur). After 
eliminating  the  displayed  errors,  this  item  will  cease  to  be  displayed.  To  view  already  not 
displayed errors, you should press ESC and ENTER keys simultaneously, when the default 
screen of the SCMI-01.4 module is displayed. You must press these keys in the given order, 
i.e. first press and hold ESC key and then press also the ENTER key. The display shows: 
 
   Err -1 
   AABBCCDD 
 
The number –1 after the title Error identifies the last (previous) error and the second line is 
the same as when displaying the current error, i.e. four two-digit hexadecimal error codes (or 
the sum of these codes, if multiple errors occur). You can use the ▼/▲ keys to display other 
previous errors with numbers from –2 to –8, i.e. it is possible to display up to eight previous 
errors.  If  the  number  of  errors  stored  in  the  SCMI-01.4  module  memory  is  lower  than  8, 
horizontal  dashes  will  be  displayed  instead  of  error  codes  in  the  empty  positions.  If  the 
number of previous errors exceeds 8, all stored error records are shifted and the oldest one 
is deleted. In this way, the error list is updated whenever a new error occurs and it cannot be 
deleted nor changed by another way. Summary of errors is given in the following tables: 
 
Errors displayed in the AA position 
E4 
01 
Compressor discharge high-temperature protection 
 
02 
Lack of refrigerant protection 
 
04 
Fan DC motor protection  
 
08 
4-way valve protection 
 
10 
Overcurrent protection 
H3 
20 
Overload protection 
E3 
40 
Compressor low pressure protection 
E1 
80 
Compressor high pressure protection 
 
Errors displayed in the BB position 
 
01 
Indoor unit freezing protection 
F3 
02 
Outdoor ambient temperature sensor malfunction 
F4 
04 
Discharge temperature sensor malfunction 
F2 
08 
Condenser temperature sensor malfunction 
 
10 
Condenser inlet tube temperature sensor malfunction 
C5 
20 
Invalid power code (invalid position of the jumper) 
 
40 
Drive unit memory chip malfunction 
 
80 
 
 
Errors displayed in the CC position 
 
01 
Protection against starting compressor at a low frequency at a low voltage 
 
02 
DC Bus overvoltage protection 
 
04 
AC current protection 
 
08 
IPM protection 
 
10 
PFC protection 
 
20 
Start up malfunction 
 
40 
Compressor wrong phase order protection 
 
80 
Drive unit module sensor malfunction