User Manual of A90 Series Inverter
298
3)
Command word for change of set frequency (e.g. 50.00Hz/1388H) (F00.04=7)
Send: 01 41 70 15 13 88 3B 97
Return:
01 41 70 15 13 88 3B 97 (normal)
Return:
01 C1 04 70 53 (exception, assuming a slave fault)
1)
Read the information of the last fault (read the function codes F19.00 to F19.05).
Send:
01 03 13 00 00 06 C1 4C
Return:
01 03 0C 00 11 00 00 00 00 01 2C 00 00 00 0053 5B (normal)
Return:
01 83 04 40 F3 (exception, assuming a slave fault)
Register value Hi
(F19.00)
Register value Lo
(F19.00)
Register value Hi
(F19.01)
Register value Lo
(F19.01)