User Manual of A90 Series Inverter
95
protection time
F10
Communication function group
F10.00
Local Modbus
communication
address
1-247; 0: broadcast address
1
F10.01
Baud rate of Modbus
communication
0: 4800
1: 9600
2: 19200
3: 38400
4: 57600
5: 115200
1
F10.02
Modbus data format
0: 1-8-N-1 (1 start bit + 8 data bits
+ 1 stop bit)
1: 1-8-E-1 (1 start bit + 8 data bits
+ 1 even parity check bit + 1 stop
bit)
2: 1-8-O-1 (1 start bit + 8 data bits
+ 1 odd parity check bit + 1 stop
bit)
3: 1-8-N-2 (1 start bit + 8 data bits
+ 2 stop bits)
4: 1-8-E-2 (1 start bit + 8 data bits
+ 1 even parity check bit + 2 stop
bits)
5: 1-8-O-2 (1 start bit + 8 data bits
+ 1 odd parity check bit + 2 stop
bits)
0
F10.03
Modbus
communication
timeout
0.0~60.0; 0.0: invalid (valid for
master-slave mode)
s
0.0
F10.04
Modbus response
delay
1 - 20
ms
2
F10.05
Options of
master-slave
communication
function
0: Invalid
1: valid
0
F10.06
Master-slave options
0: slave
1: host (Modbus protocol
broadcast transmission)
2: host (CANSinee protocol)
0
F10.07
Data sent by host
0: output frequency
1: set frequency
2: output torque
1