Rough-In | Not Applicable |
Close water supply stops before proceeding with battery replacement.
Loosen retaining screw with hex wrench and remove battery compartment cap.
Remove old battery, dispose properly, and prepare for new battery insertion.
Observe a three (3) minute waiting period before inserting the new battery.
Insert new 6 Volt CR-P2 lithium battery and reinstall the battery cover.
Open the water supply stops to restore faucet operation after battery replacement.
Troubleshoot faucet not functioning due to sensor obstruction or 'Permanent Off' mode.
Address faucet issues causing uncontrolled water delivery or abnormal operation.
Resolve no water delivery when solenoid clicks by checking supply stops and strainers.
Troubleshoot no water delivery without solenoid click, indicating a low battery condition.
Diagnose slow flow or dribble by checking supply stops, strainers, and aerator clogs.
Address faucet not stopping delivery or dripping after use, possibly due to solenoid failure.
Identify flashing LED indicator as a symptom of a low battery power level.
Troubleshoot water temperature by adjusting supply stops or the integral mixing valve.