EasyManua.ls Logo

SMA SB3.0-1SP-US-41 - Triggering Thresholds and Tripping Time; General Data

SMA SB3.0-1SP-US-41
75 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Technical Data
SMA Solar Technology AG
Installation ManualSBxx-1SP-US-41-IA-xx-1070
10.4 Triggering Thresholds and Tripping Time
Rated power fre-
quency
Triggering threshold Triggering frequency Tripping time
60 Hz > 60.5 Hz 60.45 Hz to 60.55 Hz max. 0.1602 s
< 57Hz to 59.8Hz
(Standard: 59.3Hz)
56.95Hz to 59.85Hz
(Standard: 59.25Hz
to 59.35Hz)
Adjustable: 0.16s to
300s
(Standard: max.
0.1602s)
< 57.0 Hz 56.95 Hz to 57.05 Hz max. 0.1602s
Rated grid volt-
age
Triggering
threshold - Trig-
gering voltages
Triggering volt-
age - Neutral
conductor
Triggering volt-
age - L1 and L2
Tripping time
208V 50% 57.6V to 62.4V 99.8V to
108.2V
max. 0.1602s
88% 103.2V to
108.0V
178.9V to
187.2V
max. 2.002s
110% 129.6V to
134.4V
224.6V to
233.0V
max. 1.001s
120% 141.6V to
146.4V
245.4V to
253.8V
max. 0.1602s
240V 50% 57.6V to 62.4V 115.2V to
124.8V
max. 0.1602s
88% 103.2V to
108.0V
206.4V to
216.0V
max. 2.002s
110% 129.6V to
134.4V
259.2V to
268.8V
max. 1.001s
120% 141.6V to
146.4V
283.2V to
292.8V
max. 0.1602s
Measuring precisions:
Triggering threshold: ±2% of the rated grid voltage
Tripping time: ±1% of the nominal tripping time
Triggering frequency: ±0.2% of rated power frequency
10.5 General Data
Width x height x depth 535mmx730mmx198mm
(21.1 in x 28.7 in x 7.8 in)
Weight 26 kg (57.32 lbs)
ENGLISH

Table of Contents

Related product manuals