EasyManua.ls Logo

SMA SB3.0-1SP-US-41 - Fan (Only with Sunny Boy 7.0-US; 7.7-US); Protective Devices; Torques

SMA SB3.0-1SP-US-41
75 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Technical Data
SMA Solar Technology AG
Installation ManualSBxx-1SP-US-41-IA-xx-1072
10.6 Fan (only with Sunny Boy 7.0-US / 7.7-US)
Width x height x depth 60mmx 60mmx 25.4mm
(2.36 in x 2.36 in x 1 in)
Maximum operating altitude 3000m (9843ft)
Air flow rate ≥40m³/h
10.7 Protective Devices
DC reverse polarity protection Short-circuit diode
AC short-circuit current capability Current control
Grid monitoring SMA Grid Guard 4.0
Maximum overcurrent protection 50A
Ground fault monitoring SB3.0-1SP-US-41 Insulation monitoring: R
iso
>600kΩ
Ground fault monitoring SB3.8-1SP-US-41 Insulation monitoring: R
iso
>600kΩ
Ground fault monitoring SB5.0-1SP-US-41 Insulation monitoring: R
iso
>600kΩ
Ground fault monitoring SB6.0-1SP-US-41 Insulation monitoring: R
iso
>500kΩ
Ground fault monitoring SB7.0-1SP-US-41 Insulation monitoring: R
iso
>429kΩ
Ground fault monitoring SB7.7-1SP-US-41 Insulation monitoring: R
iso
>391kΩ
All-pole sensitive residual-current monitoring unit Available
Arc fault detection AFCI, type 1, listed accord-
ing to UL1699B
Available
RapidShutdownEquipment Self discharge at all DC and AC connection
lines < 30V
10.8 Torques
Screw M5x60 for securing the inverter to the
wall mounting bracket
1.7Nm ± 0.3 Nm (15.05in-lb ± 2.65in-lb)
Screws for attaching the enclosure lid of the
Connection Unit
3Nm ± 0.3Nm (26.55in-lb ± 2.65in-lb)
Screws for grounding at equipment grounding
terminals
6Nm ± 0.3Nm (53.10in-lb ± 2.65in-lb)
Screws for SPS terminal block for connecting
the outlet for secure power supply operation
0.3Nm (2.65in-lb)
ENGLISH

Table of Contents