5 Mounting
SMA Solar Technology AG
Operating manual STP15-25TL-30-BE-en-17 21
Dimensions for mounting:
638
432
216 216
20
Ø 11
112
105 110
86 130 86
467
619
40
130
648
507
11
Figure 4: Position of the anchoring points(Dimensions in mm)
Recommended clearances:
If you maintain the recommended clearances, adequate heat dissipation will be ensured. Thus, you
will prevent power reduction due to excessive temperature.
Maintain the recommended clearances to walls as well as to other inverters or objects.
If multiple products are mounted in areas with high ambient temperatures, increase the
clearances between the products and ensure sufficient fresh-air supply.