EasyManua.ls Logo

SMA STP 17000TL-30 - Page 77

SMA STP 17000TL-30
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11 Disconnecting the Inverter from Voltage Sources
SMA Solar Technology AG
Operating manual STP15-25TL-30-BE-en-17 77
7. Pull the DC load-break switch down and out of the
recess.
8. Remove all six screws from the lower enclosure lid
using an Allen key (AF 3).
9. Lift and remove the lower enclosure lid from below.
10.
CAUTION
Risk of burns when touching the DC protective cover
The DC protective cover can get hot during operation.
Do not touch the DC protective cover.
11. Release and remove all DC connectors. Insert a
slotted screwdriver or an angled screwdriver (blade
width 3.5mm) into one of the slide slots and pull the
DC connectors out downwards. Do not pull on the
cable.
1
2
12. Ensure that no voltage is present at the DC inputs of the inverter.