Electrical Connection SMA Solar Technology AG
24 SMC6-8TL-IEN101040 Installation Guide
Cable Requirements
Load Disconnection Unit
You must install a separate line circuit breaker for each inverter in order to ensure that the inverter
can be securely disconnected under load. The maximum permissible rating is located in section
11”Technical Data” (page74).
Detailed information and examples for the rating of a line circuit breaker can be found in the Technical
Information "Line Circuit Breaker" in the SMA Solar Technology AG download area at
www.SMA.de/en.
Position Description Value
A External diameter 12 mm … 25 mm
B Conductor cross-section 10 mm² … 16 mm²
C Strip insulation Approx. 16 mm
DANGER!
Danger to life due to fire.
When more than one inverter is connected to the same line circuit breaker, the protective
function of the line circuit breaker is no longer guaranteed. It can result in a cable fire or
the destruction of the inverter.
Never connect several inverters to the same line circuit breaker.
Comply with the maximum permissible fuse protection of the inverter when selecting
the circuit breaker.