SMA Solar Technology AG Technical Data
Installation Guide SMC6-8TL-IEN101040 75
Mechanical data
Climatic Conditions
* according to DIN EN 50178:1998-04, installation type C, class 4K4H
** according to DIN EN 50178:1998-04, transport type E, class 2K3
Features
General data
Test voltage (DC) 2.15 kV
Test surge voltage 4 kV
Surge testing voltage with serial interface 6 kV
Internal consumption in night mode 0.25 W
Width x height x depth 468 mm x 613 mm x 242 mm
Weight 31 kg
Extended temperature range * − 25 °C … +60 °C
Extended humidity range * 0 % … 100 %
Extended air pressure range * 79.5 kPa … 106 kPa
Temperature range ** − 25 °C … +70 °C
Operation temperature range − 25 °C … +60 °C
Maximum operating altitude above mean sea
level
3,000 m
Topology Transformerless
Cooling concept OptiCool
Fan connection Designed for safe disconnection
In accordance with DIN EN 50178:1998-04
Protection rating in accordance with
DIN EN 60529
IP65
Protection class I
Noise emission (typical) ≤ 31 dB(A)