Failure Search SMA Solar Technology AG
62 SMC6-8TL-IEN101040 Installation Guide
Message Description and corrective measure
!PV-Overvoltage!
!DISCONNECT DC!
Overvoltage at DC input.
Overvoltage can destroy the inverter.
Corrective measures
Disconnect the inverter from the grid immediately.
1. Turn off the line circuit breaker.
2. Remove the Electronic Solar Switch.
3. Disconnect all the DC plug connectors.
4. Check DC voltage:
If the DC voltage exceeds the maximum input voltage, check the
plant design or contact the person who installed the PV
generator.
If the DC voltage is under the maximum input voltage, reconnect
the inverter to the PV generator as described in section
5.4.4”Connecting the PV Generator (DC)” (page34).
If the message occurs again, disconnect the inverter again and contact
the SMA Serviceline (see section 13”Contact” (page85)).
ACVtgRPro The 10-minute-average grid voltage is no longer within the permissible
range. This can have the following causes:
The grid voltage at the connection point is too high.
The grid impedance at the connection point is too high.
The inverter disconnects to assure compliance with the voltage quality of
the grid.
Corrective measures
Check the grid voltage at the connection point of the inverter:
If, due to the local grid conditions, the grid voltage is 253 V or
more, ask the utility operator whether the voltage at the feed-in
point can be adjusted, or whether it would agree to an alteration of
the threshold value of the ACVtgRPro parameter to monitor the
voltage quality.
If the grid voltage is continually within the acceptable range and
this error is still displayed, contact the SMA Serviceline
CAN Internal communication fault.
Corrective measures
If this fault occurs often, contact the SMA Serviceline