ACC4100 Diesel Air Compressor Controller User Manual Page 39 of 52
Set Val: +00098
next bit. After setting finished, press to enter delay setting. If it is not
need to modify, press to return.
Delay 00003s
NOTES:
Please modify internal parameters (eg: Crank disconnect conditions, programmable input/output configuration,
delay, etc) in standby status, otherwise it probably shutdowns or faults may occur;
Over high threshold must be greater than lower threshold, otherwise over high and over low circumstances may
occur simultaneously;
Please set return value correctly when warning alarm is set, otherwise the controller can’t alarm normally. When
over warning is set, the return value should be set lower than set value; when low warning is set, return value should
be set greater than set value;
Programmable inputs can’t be set the same item (except for user-defined), otherwise it won’t arise valid function.
But programmable outputs can be set the same.