APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 55 of 62
12.9 DEUTZ EMR2
Terminals of controller
F connector
Remark
Fuel relay output
Expand 30A relay, battery
voltage of 14 is supplied
by relay. Fuse is 16A.
Start relay output
-
Connect to starter coil directly
-
1
Connect to battery negative pole
CAN GND
-
CAN communication shielding
line(connect with controllers
terminal only)
CAN(H)
12
Impedance 120Ω connecting
line is recommended.
CAN(L)
13
Impedance 120Ω connecting
line is recommended.
Engine type: VolvoEDC4
12.10 JOHN DEERE
Terminals of controller
21 pins connector
Remark
Fuel relay output
G,J
Start relay output
D
CAN GND
-
CAN communication shielding
line(connect with controllers
terminal only)
CAN(H)
V
Impedance 120Ω connecting
line is recommended.
CAN(L)
U
Impedance 120Ω connecting
line is recommended.
Engine type: John Deere
12.11 MTU MDEC
Suitable for MTU engines, 2000 series, 4000series
Terminals of controller
X1 connector
Remark
Fuel relay output
BE1
Start relay output
BE9
CAN GND
E
CAN communication shielding
line(connect with one
terminal only)
CAN(H)
G
Impedance 120Ω connecting
line is recommended.
CAN(L)
F
Impedance 120Ω connecting
line is recommended.
Engine type: MTU-MDEC-303