APC715 Pump Unit Controller
APC715 Pump Unit Controller ISSUE 2013-08-28 Version 1.0 Page 45 of 62
7.4 SELECTION OF SENSORS
No.
Description
Remark
1
Temperature
Sensor
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO
4 CURTIS
5 VOLVO-EC
6 DATCON
7 SGX
8 SGD
9 SGH
10 PT100
11~15 Reserved
Defined resistance’s
range is (0~6)KΩ,
default is SGX sensor.
2
Pressure Sensor
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO 10Bar
4 CURTIS
5 VOLVO-EC
6 DATCON 10Bar
7 SGX
8 SGD
9 SGH
10~15 Reserved
Defined resistance’s
range is (0~6)KΩ,
default is SGX sensor.
3
Fuel Level
Sensor
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 SGD
4 SGH
5~15 Reserved
Defined resistance’s
range is (0~6)KΩ,
default is SGH sensor.
Note: User should take the controller apart to change the jumper hat from resistor
side to current side if your pump unit fitted with 4~20mA sensor.