No. DOC1045423
IO-Link master unit (EX600-L#B1) (continued)
Index
Name (Meaning)
Type
Value
40x5:0
2
Port1-Port power off/on
UNSIGNED8
2
40x5:01
2
Port Power Mode
Enum0815
0 = One time switch off
(Power Off Time)
1 = Switch PortPowerOff
2 = Switch PortPowerOn
40x5:02
2
Power Off Time
UNSIGNED16
0x01F4 to 0xFFFF (msec)
40x6:0
2
Port2-Port power off/on
See Port1-PortPower off/on
40x7:0
2
Port3-Port power off/on
40x8:0
2
Port4-Port power off/on
40x9:0
3
Device read/write
UNSIGNED8
6
40x9:01
3
Request
Enum0819
0 = Read
1 = Write
40x9:02
3
Port
Enum081A
0 = Port1
1 = Port2
2 = Port3
3 = Port4
40x9:03
3
Index
UNSIGNED16
Default 0
40x9:04
3
Subindex
UNSIGNED8
Default 0
40x9:05
3
Length
UNSIGNED8
Default 0
40x9:06
3
Data
Octet string
232bytes max.
40xA:0
4
L+ control
UNSIGNED8
4
40xA:01
4
Port1
Enum081B
0 = On
1 = Off
40xA:02
4
Port2
Enum081B
0 = On
1 = Off
40xA:03
4
Port3
Enum081B
0 = On
1 = Off
40xA:04
4
Port4
Enum081B
0 = On
1 = Off
1: Read only.
2: EX600-LAB1 only.
3: For details on how to operate Device read/write, see page 103.
4: EX600-LBB1 only.
Note: x = Unit No.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks EX600-ED Series and is the answer not in the manual?

SMC Networks EX600-ED Series Specifications

General IconGeneral
BrandSMC Networks
ModelEX600-ED Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals