VOLTAGE CONFIGURATIONS (continued)
ELECTRONIC MODULE CONNECTIONS
The Voltage sensing kit provides power
and sensing to the electronic module
from the generator and the main side.
Main sensing is 3 phases sensing:
103: Neutral
104: Phase 3
105: Phase 2
106: Phase 1
Gen sensing is single phase sensing:
203: Phase 1
205: Phase 3
A. No wiring change required from standard delivery
Configurations:
V502 415/240 Vac 50 Hz
V503 400/230 Vac 50 Hz
V504 380/220 Vac 50 Hz
V603 440/254 Vac 60 Hz
V605 380/220 Vac 60 Hz
V601 480/277 Vac 60 Hz - Special Voltage Option 5 = 277Vac
3 Phases 4 Wires connections-3P4L
Verify voltage between
101/102 & 201/202
= 220/240 Vac±20%
ATI 059 B GB