EasyManua.ls Logo

socomec DIRIS Digiware M-70 - Page 18

socomec DIRIS Digiware M-70
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18 EN
DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC
4b 5b
3 3
Digiware Bus
U-xx
I-xx
1
ALARM
ON
COM
ADDR.
ETHETH
DIRIS M-xx
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLY
RS485
NC
ALARM
ON
COM
ADDR.
ETHETH
DIRIS M-xx
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLY
RS485
NC
ALARM
ON
COM
ADDR.
ETHETH
DIRIS M-xx
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLY
RS485
NC
ALARM
ON
COM
ADDR.
ETHETH
DIRIS M-xx
ETHDIGIWARE
BUS
24 V
20 W max
SUPPLY
RS485
NC
2 2
Flashing LED Stable LED
Steps involved in the auto-discovery process:
Press
3 sec.
≤ 120 sec
3
Press
3 sec.
4a
Press
3 sec.
5a
6
1. Start the auto-discovery of all devices connected to the Digiware or RS485 buses, by pressing the ADDR. button
for 3 seconds.
2. “COM” LEDs of all devices will start blinking synchronously during the process. If com LEDs are not blinking, there
could be a conguration issue (inconsistent baudrate between M-xx gateway and slave device etc.).
3. After approximately 1 minute, some address conicts have been detected, and the COM LED of the M-xx gateway
as well as slave devices is lit and stable.
4a/5a. Press the front button on each slave device that has a xed COM LED, for at least 2 seconds.
4b/5b. COM LEDs of the modules start blinking again.
6. COM LED of the M-xx gateway starts blinking again, and slave devices can now communicate with the M-xx
gateway.