8. 6. Unit statUs: addrEss 0x1143, 4 words
Code Description Bit Address Remarks
S048 Load on inverter 0 0x1143
S049 Load on auto. Bypass 1
S050 Load on maintenance Bypass 2
S051 Load not supplied 3
S052 Unit is available 4
S053 Unit isolated from inst. 5
S054 Output switch Q2/3 closed 6
S055 Rectier ON 7
S056 Battery charging 8
S057 Battery charged 9
S058 10
S059 Inverter ON 11
S060 Inverter switch/contactor closed 12
S061 Bypass switch activated 13
S062 14
S063
Servicing alert
15
S064
Rectier input supply fault
0 0x1144
S065 Bypass input supply out of tolerance 1
S066 Bypass input supply failure V/F 2 2
S067 Bypass input supply is synchro ref 3
S068 Ext. synchro ref (ACS on) 4
S069 Synchro forced on ACS 5
S070 “UPS general power off” input active 6
S071 Generator set active 7
S072 Unit in normal mode 8
S073 Unit in eco-mode 9
S074 10
S075 Unit in stand-by mode 11
S076 12
S077 13
S078 14
S079 Unit in servicing mode 15
sIngle UnIt UPs modbUs tables
14
Delphys green power - Ref.: