SE4K SE5K SE7K SE8K SE9K SE10K SE12.5K Unit
Protective class Class I
Utility monitoring,
islanding protection,
configurable Power
Factor, country
configurable
thresholds
Yes
Overvoltage category III
Input
Maximum DC power
(Module STC)
5400 6750 9450 10800 12150 13500 16850 W
Transformer-less,
ungrounded
Yes
Maximum input
voltage
900 Vdc
Nominal DC input
voltage
750 Vdc
Maximum input
current
7 8.5 12 13.5 15 16.5 21 Adc
Maximum back-feed
current
0 Adc
Reverse-polarity
protection
Yes
Ground-fault
isolation detection
700kΩ Sensitivity
Overvoltage category II
Maximum inverter
efficiency
98 %
European weighted
efficiency
97.3 97.3 97.3 97.5 97.5 97.6 97.7 %
Night-time power
consumption
< 2.5 W