EasyManua.ls Logo

SolarEdge SE16K

SolarEdge SE16K
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SE2200 SE3000 SE3500 SE4000
SE4000-
16A
SE5000 SE6000 Unit
Overvoltage category III
Input
Maximum DC power
(Module STC)
2950 4050 4700 5400 5000 6750 8100 W
Transformer-less,
ungrounded
Yes
Maximum input
voltage
500 Vdc
Nominal DC input
voltage
350 Vdc
Maximum input
current
8.5 11.5 13.5 15.5 15.5 19.5 23 Adc
Maximum back-feed
current
0 Adc
Reverse-polarity
protection
Yes
Ground-fault
isolation detection
600 kΩ Sensitivity
Overvoltage category II
Maximum inverter
efficiency
97.6 %
European weighted
efficiency
97.6 97.6 97.5 97.5 97.5 97.4 97.4 %
Night-time power
consumption
< 2.5 W
Additional Features
Supported
communication
interfaces
(1)
RS485, RS232, Ethernet, ZigBee (optional), Built-in GSM
(optional)
Smart Energy
Management
Export Limitation, StorEdge applications
Standard Compliance
Safety IEC-62103 (EN50178), IEC-62109
Grid connection
standards
VDE-AR-N-4105, VDE 0126-1-1, AS-4777, RD-1663, DK 5940
(1)
Refer to Datasheets -> Communications category in Downloads page for specifications of optional communication
options: http://www.solaredge.com/groups/support/downloads