SE15K SE16K SE17K SE25K SE27.6K SE33.3K Unit
Grid connection
standards
(1)
VDE-AR-N-4105, G59/3, AS-4777, EN 50438 , VDE 0126-
1-1, CEI-021,
BDEW, CEI-016
(2)
;
Emissions
IEC61000-6-2, IEC61000-6-3, IEC61000-3-11, IEC61000-3-
12
WEEE, RoHS Yes
Installation Specifications
AC output / Gland
Diameter / Wire Cross
Section
15-21 mm / Solid wire 2.5-
16 mm
2
,
Stranded wire 2.5 - 10
mm
2
18-25mm / Solid wire 2.5-16
mm
2
,
Stranded wire 2.5-10 mm
2
DC input
(3)
2 MC4 pairs 3 MC4 pairs
DC input with DC
Safety Unit
N/A
Gland diameter 5-10 mm mm
Wire cross section 0.5 - 13.5 mm
2
Dimensions (HxWxD) 540 x 315 x 260 mm
Dimensions with
Safety Unit (HxWxD)
N/A 775 x 315 x 260 mm
Weight 33.2 45 kg
Weight with Safety
Unit
N/A 48 kg
Operating
temperature range
(4)
-20 - +60 (M40 version -40 to + 60) °C
Operating humidity –
non condensing
< 95 %
Cooling Fan (user replaceable)
Noise (typical) < 50 < 55 dBA
Protection rating/
Environmental
category
IP65 Outdoor and indoor
Maximum altitude 2000 m
(1)
For all standards refer to the Certifications category in
http://www.solaredge.com/groups/support/downloads.
(2)
Models SE25K, SE27.6Kand SE33.3K only
(3)
Connection of additional strings in parallel to a single input is allowed as long as the cumulative current does not
exceed 45A.
(4)
For inverter power de-rating information, refer to the application note at the following link:
http://www.solaredge.com/files/pdfs/se-temperature-derating-note.pdf
Technical Specifications - Three Phase Inverters (Europe &APAC) 111
Three Phase System Installation Guide MAN-01-00057-4.1