What to do if Solplanet Inverter displays error code 65?
- JJennifer ScottSep 23, 2025
If your Solplanet Inverter displays error code 65, check if the ground line is properly connected to the inverter.
What to do if Solplanet Inverter displays error code 65?
If your Solplanet Inverter displays error code 65, check if the ground line is properly connected to the inverter.
What to do if Solplanet ASW S Inverter shows Presumable Fault 41, 42, 43, 44, 45, 47?
If your Solplanet Inverter is showing Presumable Fault 41, 42, 43, 44, 45, or 47, disconnect the inverter from the grid and the PV array. Wait for 3 minutes, then reconnect it. If the fault continues to display, further assistance is needed.
What to do if Solplanet ASW S shows Presumable Fault 35?
If your Solplanet Inverter displays Presumable Fault 35, check the fuse and the circuit breaker in the distribution box. Also, verify the grid voltage and usability, and inspect the AC cable and grid connection on the inverter. If the fault persists, further assistance is needed.
What to do if Solplanet ASW S Inverter shows Presumable Fault 34?
If your Solplanet Inverter shows Presumable Fault 34, start by checking the grid voltage and the grid connection on the inverter. Verify the grid voltage at the point where the inverter connects. If the grid voltage is outside the acceptable range due to local grid conditions, you might need to adjust the monitored operational limits, but only after informing your electric utility company. If the grid voltage is within the permitted range and the fault continues, further assistance is needed.
How to fix Presumable Fault 38 on Solplanet Inverter?
To address Presumable Fault 38 on your Solplanet Inverter, check the PV array’s insulation to ground, ensuring it exceeds 1 MOhm. Conduct a visual inspection of all PV cables and modules. Also, confirm that the inverter's grounding connection is secure. If the fault frequently occurs, further assistance is needed.
What to do if Solplanet Inverter displays error codes 61, 62?
If your Solplanet Inverter displays error codes 61 or 62, check the DRED device communication or operation.
What to do if Solplanet Inverter displays error code 33?
If your Solplanet Inverter displays error code 33, check the grid frequency and observe how often major fluctuations occur. If the fault is caused by frequent fluctuations, you can try to modify the operating parameters, but only after informing the grid operator first.
What to do if Solplanet ASW S Inverter displays error code 35?
If your Solplanet Inverter displays error code 35, check the fuse and the triggering of the circuit breaker in the distribution box.
What to do if Solplanet ASW S displays error code 36?
If your Solplanet Inverter displays error code 36, ensure the grounding connection of the inverter is reliable. Perform a visual inspection of all PV cables and modules. If the error continues to appear after these steps, contact the service.
What to do if Solplanet Inverter shows error codes 41, 42, 43, 44, 45, 47?
If your Solplanet Inverter displays error codes 41, 42, 43, 44, 45, or 47, disconnect it from both the grid and the PV array. Wait for 3 minutes, and then reconnect it. If the fault persists, it is recommended to contact the service.
General information about the Solplanet inverter.
Specifies the inverters covered by this manual.
Identifies qualified electricians as the intended audience.
Explains safety symbols used throughout the manual.
Details the proper applications and limitations of the inverter.
Highlights critical safety precautions for operation and installation.
Explains various symbols found on the inverter's label.
Lists all components included in the inverter package.
Provides instructions on inspecting the packaging for damage.
Specifies environmental requirements for inverter installation.
Guides on choosing an appropriate installation site for the inverter.
Details the procedure for mounting the inverter using the provided bracket.
Emphasizes crucial safety measures for electrical connections.
Explains the electrical connection layout for specific inverter configurations.
Identifies and explains the various connection ports on the inverter.
Details the procedure for connecting the inverter to the AC power grid.
Step-by-step guide for connecting the inverter to the electricity grid.
Instructions for establishing a second protective ground connection.
Specifies requirements for PV modules and string configuration.
Guides on how to assemble and safely disassemble DC connectors.
Steps for correctly connecting the PV array to the inverter.
Explains how to monitor the inverter using RS485 or Ethernet.
Details how to monitor the inverter using a WLAN connection.
Information on demand response capabilities and modes.
How to control active power using smart meters and communication modules.
How the inverter communicates with external devices.
Explains the earth fault alarm function and indicators.
Procedures for performing electrical tests before commissioning.
Checks to ensure the inverter's physical integrity and waterproofing.
Steps for verifying and setting the safety code.
Procedure for initiating the inverter's operation.
General overview of the inverter's control panel and indicators.
Detailed explanation of the function of each LED indicator.
Specifications related to the DC input parameters of the inverter.
Specifications related to the AC output parameters of the inverter.
Comprehensive list of general specifications for the inverter.
Details the safety standards and protective devices integrated into the inverter.
Lists required tools and torque specifications for installation.
Provides solutions for common operational problems and error codes.
Annual procedure for cleaning the DC switch contacts.
Instructions for cleaning the inverter's heat sink.
| Number of MPPT | 2 |
|---|---|
| Total Harmonic Distortion | < 3 % |
| DC Connection Type | MC4 |
| Protection Degree | IP65 |
| Cooling Method | Natural Convection |
| Max Input Current per MPPT | 12.5A |
| Rated AC Voltage | 230V |
| Output Voltage Range | 180 V - 280 V |
| Rated Grid Frequency | 50 Hz / 60 Hz |
| Operating Temperature Range | -25°C to +60°C |
| Communication | WiFi, Ethernet, RS485 |
| AC Connection Type | Plug-in terminal |