Questions and Answers

  • T
    Theresa MathisSep 23, 2025
    What to do if Solplanet Inverter displays error code 65?
    • J
      Jennifer ScottSep 23, 2025
      If your Solplanet Inverter displays error code 65, check if the ground line is properly connected to the inverter.
  • T
    Thomas DavisAug 23, 2025
    What to do if Solplanet ASW S Inverter shows Presumable Fault 41, 42, 43, 44, 45, 47?
    • G
      Gabrielle HolmesAug 23, 2025
      If your Solplanet Inverter is showing Presumable Fault 41, 42, 43, 44, 45, or 47, disconnect the inverter from the grid and the PV array. Wait for 3 minutes, then reconnect it. If the fault continues to display, further assistance is needed.
  • C
    Christopher KimAug 25, 2025
    What to do if Solplanet ASW S shows Presumable Fault 35?
    • S
      Sarah MartinezAug 26, 2025
      If your Solplanet Inverter displays Presumable Fault 35, check the fuse and the circuit breaker in the distribution box. Also, verify the grid voltage and usability, and inspect the AC cable and grid connection on the inverter. If the fault persists, further assistance is needed.
  • R
    Roberto HallAug 27, 2025
    What to do if Solplanet ASW S Inverter shows Presumable Fault 34?
    • J
      Jason AndersonAug 27, 2025
      If your Solplanet Inverter shows Presumable Fault 34, start by checking the grid voltage and the grid connection on the inverter. Verify the grid voltage at the point where the inverter connects. If the grid voltage is outside the acceptable range due to local grid conditions, you might need to adjust the monitored operational limits, but only after informing your electric utility company. If the grid voltage is within the permitted range and the fault continues, further assistance is needed.
  • S
    Steven HarrisAug 27, 2025
    How to fix Presumable Fault 38 on Solplanet Inverter?
    • D
      Denise YoungAug 28, 2025
      To address Presumable Fault 38 on your Solplanet Inverter, check the PV array’s insulation to ground, ensuring it exceeds 1 MOhm. Conduct a visual inspection of all PV cables and modules. Also, confirm that the inverter's grounding connection is secure. If the fault frequently occurs, further assistance is needed.
  • W
    william07Sep 18, 2025
    What to do if Solplanet Inverter displays error codes 61, 62?
    • A
      Ashley WilliamsSep 18, 2025
      If your Solplanet Inverter displays error codes 61 or 62, check the DRED device communication or operation.
  • D
    David SimmonsSep 15, 2025
    What to do if Solplanet Inverter displays error code 33?
    • R
      Russell SmithSep 15, 2025
      If your Solplanet Inverter displays error code 33, check the grid frequency and observe how often major fluctuations occur. If the fault is caused by frequent fluctuations, you can try to modify the operating parameters, but only after informing the grid operator first.
  • V
    valerie58Sep 16, 2025
    What to do if Solplanet ASW S Inverter displays error code 35?
    • J
      John HesterSep 16, 2025
      If your Solplanet Inverter displays error code 35, check the fuse and the triggering of the circuit breaker in the distribution box.
  • T
    tlaneSep 6, 2025
    What to do if Solplanet ASW S displays error code 36?
    • F
      falvaradoSep 7, 2025
      If your Solplanet Inverter displays error code 36, ensure the grounding connection of the inverter is reliable. Perform a visual inspection of all PV cables and modules. If the error continues to appear after these steps, contact the service.
  • J
    Jamie ThompsonSep 4, 2025
    What to do if Solplanet Inverter shows error codes 41, 42, 43, 44, 45, 47?
    • H
      hschmidtSep 4, 2025
      If your Solplanet Inverter displays error codes 41, 42, 43, 44, 45, or 47, disconnect it from both the grid and the PV array. Wait for 3 minutes, and then reconnect it. If the fault persists, it is recommended to contact the service.

Summary

Notes on this Manual

General Notes

General information about the Solplanet inverter.

Area of Validity

Specifies the inverters covered by this manual.

Target Group

Identifies qualified electricians as the intended audience.

Symbols Used in this Manual

Explains safety symbols used throughout the manual.

Safety

Intended Use

Details the proper applications and limitations of the inverter.

Important Safety Information

Highlights critical safety precautions for operation and installation.

Symbols on the Label

Explains various symbols found on the inverter's label.

Unpacking

Scope of Delivery

Lists all components included in the inverter package.

Checking for Transport Damage

Provides instructions on inspecting the packaging for damage.

Mounting

Ambient Conditions

Specifies environmental requirements for inverter installation.

Selecting the Mounting Location

Guides on choosing an appropriate installation site for the inverter.

Mounting the Inverter with the Wall Bracket

Details the procedure for mounting the inverter using the provided bracket.

Electrical Connection

Safety

Emphasizes crucial safety measures for electrical connections.

System Layout without Integrated DC Switch

Explains the electrical connection layout for specific inverter configurations.

Overview of Connection Area

Identifies and explains the various connection ports on the inverter.

AC Connection

Details the procedure for connecting the inverter to the AC power grid.

Grid Connection

Step-by-step guide for connecting the inverter to the electricity grid.

Second Protective Grounding Connection

Instructions for establishing a second protective ground connection.

DC Connection Requirements

Specifies requirements for PV modules and string configuration.

Assembling and Disassembling DC Connectors

Guides on how to assemble and safely disassemble DC connectors.

Connecting the PV Array

Steps for correctly connecting the PV array to the inverter.

Communication

System Monitoring via RS485;Ethernet

Explains how to monitor the inverter using RS485 or Ethernet.

System Monitoring via WLAN

Details how to monitor the inverter using a WLAN connection.

Inverter Demand Response Modes (DRED)

Information on demand response capabilities and modes.

Active Power Control with Smart Meter & AiCom;AiManager

How to control active power using smart meters and communication modules.

Communication with Third-Party Devices

How the inverter communicates with external devices.

Earth Fault Alarm

Explains the earth fault alarm function and indicators.

Commissioning

Electrical Checks

Procedures for performing electrical tests before commissioning.

Mechanical Checks

Checks to ensure the inverter's physical integrity and waterproofing.

Safety Code Check

Steps for verifying and setting the safety code.

Start-Up

Procedure for initiating the inverter's operation.

Operation

Overview of the Panel

General overview of the inverter's control panel and indicators.

LEDs

Detailed explanation of the function of each LED indicator.

Disconnecting the Inverter from Voltage Sources

Technical Data

DC Input Data

Specifications related to the DC input parameters of the inverter.

AC Output Data

Specifications related to the AC output parameters of the inverter.

General Data

Comprehensive list of general specifications for the inverter.

Safety Regulations

Details the safety standards and protective devices integrated into the inverter.

Tools and Torque

Lists required tools and torque specifications for installation.

Troubleshooting

Common Issues and Corrective Measures

Provides solutions for common operational problems and error codes.

Maintenance

Cleaning DC Switch Contacts

Annual procedure for cleaning the DC switch contacts.

Cleaning the Heat Sink

Instructions for cleaning the inverter's heat sink.

Recycling and Disposal

EU Declaration of Conformity

Warranty

Contact Information

Solplanet ASW S Series Specifications

General IconGeneral
Number of MPPT2
Total Harmonic Distortion< 3 %
DC Connection TypeMC4
Protection DegreeIP65
Cooling MethodNatural Convection
Max Input Current per MPPT12.5A
Rated AC Voltage230V
Output Voltage Range180 V - 280 V
Rated Grid Frequency50 Hz / 60 Hz
Operating Temperature Range-25°C to +60°C
CommunicationWiFi, Ethernet, RS485
AC Connection TypePlug-in terminal