Functions
Settings:
• Set the potentiometer for the desired time (1 - 120 seconds)
• DIP switch 7 + 8 OFF
• DIP switches 2, 4 ON
• Other DIP switches as desired
Prewarning time (DIP 5)
A warning light connected to warning light connection 1 (terminal 16 + 17)
flashes for 3 seconds after pressing the button or the handheld transmitter
before the operator starts.
The prewarning time is cancelled if a button or handheld transmitter is
actuated again.
DIP switch 5
OFF Deactivated
ON Activated, warning light 1 flashes for 3 seconds
Fraba system (DIP 6)
The function of safety connection 1 (terminal 6 + 7) can be switch to
evaluation of the signal of a Fraba system here.
DIP switch 6
OFF Deactivated
ON Activated
Denedopeningandclosing(DIP7)
IMPORTANT INFORMATION!
A combination of defined opening/closing function and
automatic closing function is possible.
Button/channel 1 open and button/channel 2 close the gate. The 2-channel
mode can also be used with only 2 buttons or with handheld remote controls.
Requirement: DIP switch 8 OFF, 2 buttons connected or 2 handheld
transmitter buttons programmed.
DIP switch 7
OFF Deactivated
ON Activated
Partial opening (DIP 8)
IMPORTANT INFORMATION!
A combination of defined partial opening function and
automatic closing function is possible.
Depending on the setting, this function partially opens the gate.
Example:
open the gate for persons to pass through. Partial opening can be used
with two buttons or by radio (handheld transmitter, Telecody, etc.).
DIP switch 8
OFF Deactivated
ON Activated, DIP switch 7 non-functional
Partial opening with 2 buttons
Install additional button and connect to terminals 4 + 5 as button 2.
Button 1 always opens the gate completely.
If the gate is partially opened with button 2, pressing button 1 opens the
gate completely.
Button 2 performs the partial opening only if the gate is closed.
If the gate is to be completely opened with button 1 or partially opened with
button 2, pressing button 2 again closes the gate.
Procedure
1. Close the gate.
2. DIP switch 8 ON: activates partial opening.
IMPORTANT INFORMATION!
Always leave DIP switch 8 set to ON, the OFF setting
immediately deletes the set partial opening.
3. Press button 2 (open door from CLOSED end position).
⇒ Door opens until button 2 is pressed again or the door reaches the
"door OPEN" end position.
4. Press button 2 once the desired position is reached.
5. Close gate with button 2.
⇒ Partial opening saved and pressing button 2 opens the gate to the
saved position.
6. Set DIP switch 8 to OFF to delete the partial opening setting.