25
Installer Setup
Cycles Per Hour (setup step 17)
The Cycles Per Hour setting may limit the number of times per hour
your HVAC unit may energize. For example, at a setting of 6 cycles
per hour the HVAC unit will only be allowed to energize once every
10 minutes. The Cycles Per Hour limit may be overridden and reset by
pressing the WARMER or COOLER buttons on the thermostat. Settings
are No Limit, 2, 3, 4, 5, or 6.
Compressor Minimum Off Minutes (setup step 18)
This feature allows the user to set a minimum off time for the
compressor. Settings are 5 mins., 3 mins., or 0 mins.
Minimum Heat/Cool Setpoint Difference (setup step 19)
This feature allows the user to set the minimum gap between Heat
and Cool setpoints in AUTO mode. Select from 0 to 6. If setup step 2 is
not set for AUTO-CHANGEOVER, this step will not appear.
Number of Heat Stages (setup step 20)
This setting assures proper stage callouts on the thermostat display
for non-heat pump applications.
Number of Cool Stages (setup step 21)
This setting assures proper stage callouts on the thermostat display
for non-heat pump applications.
Number of Aux Stages (setup step 22)
This feature is for heat pump application only.
This feature allows for proper Aux Heat Staging. (0-1 stages)