Appendix V
168
V-5-2 Connection:
The control terminals DI1 and COM are short-circuited and run forward
command (0 segment speed setting 0X). DI2, DI3 and DI4 correspond to 3-segment speed short to
COM and 100% parameter value corresponds to 50HZ.(Take the three-stage speed as an example, up
to 16-stage speed control can be realized).
V-5-3 Parameter setting:
Frequency source master
setting
Multi-speed operation setting
Terminal block control (LED on)
DI1 terminal function selection
DI2 terminal function selection
DI3 terminal function selection
DI4 terminal function selection
0-stage speed frequency setting
percentage
1-stage speed frequency setting
percentage
2-stage speed frequency setting
percentage
3-stage speed frequency setting
percentage
Multi-stage command 0
reference manner
0 ~ 7 selection, according to the
site requirements to set the
corresponding way
V-6 External potentiometer speed regulation
V-6-1 electrical diagram:
(De fault)
Circuit breaker
380/400V 50/60Hz
Threephaseinputpowersupply
FWD/STOP
Motor
M
%
Speed regulation by external potentiometer
ST500